Why S&A CWFL-6000 shows ultra-high temperature alarm (E05 or E07)?
- MmichellejacksonAug 20, 2025
The ultra-high temperature alarm on your S&A Chiller (displaying E05 or E07) can be triggered by several factors: * A blocked dust gauze preventing proper thermolysis. Clean the dust gauze regularly. * Poor ventilation around the air outlet and inlet. Ensure sufficient ventilation. * Unstable or extremely low voltage. Improve the power supply circuit or use a voltage regulator. * Incorrect thermostat parameter settings. Reset the controlling parameters or restore factory settings. * Frequent power switching. Allow sufficient time for refrigeration (more than 5 minutes). * Excessive heat load. Reduce the heat load or consider a model with larger cooling capacity.