EasyManua.ls Logo

S&A CWUL-10 - CWUL-10 Model Specifications

S&A CWUL-10
15 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CWUL-05/10/20 Series
12
CWUL-10
Mode
CWUL-10AH
CWUL-10BH
CWUL-10DH
CWUL-10AI
CWUL-10BI
CWUL-10DI
Voltage
AC 1P 220V
AC 1P 220V
AC 1P 110V
AC 1P 220V
AC 1P 220V
AC 1P 110V
Frequency
50Hz
60Hz
60Hz
50Hz
60Hz
60Hz
Current
0.25~2.3A
0.25~2.4A
0.45~4.15A
0.7~2.75A
0.7~2.75A
1~4.7A
Nominal cooling
capacity
0.81KW
0.85KW
0.85KW
0.81KW
0.85KW
0.85KW
Refrigerant
R-134a
Precision
±0.3
Reducer
Capillary
Protection
Overcurrent protection for compressor, flow alarm, over temperature alarm
Pump power
50 W
100 W
Max. lift
12M
25M
Max. flow
13L/min
16L/min
Tank capacity
6 L
N.W
24Kgs
G.W
27Kgs
Dimension
58X29X47 cm (L X W X H)
Package
dimension
70 X43X58 cm (L X W X H)
Note: The current and nominal cooling capacity could be different under different working
conditions and configurations. The above information is for reference only. Please subject to the
nameplate of the actual delivered product.The max. pump flow is obtained by testing the pump
individually on test criteria GB/T 3216-2005.