22 S&C Instruction Sheet 766-510
Operation
Status Indicator
The STATUS INDICATOR (white LED) light shows
operational status of the IntelliRupter fault interrupter.
See Figure 33.
Off:
IntelliRupter fault interrupter is not powered
IntelliRupter fault interrupter is not functioning
properly
Solid On:
If con gured by user, Remote Operation mode is
disabled
Flashes for ½ second every 30 seconds:
Normal operation
On 10 seconds, then flashes for ½ second every
30 seconds:
Wi-Fi has been disconnected
Interrupter OPEN/CLOSE/READY lever has been
moved from:
Ready to Open
– Ready to Close
– Open to Ready
GROUND TRIP BLOCK lever has been moved from:
Removed to Set
Set to Removed
Pulsates dim to bright:
Wi-Fi is connected
Flashes for ½ second every second:
Any error state is active
Settings Mismatch is active and, if con gured by
user, Battery Low, Bad or Disconnected
Flashes 3 times (½ second on, ½ second off) every
30seconds:
IntelliTeam® SG Automatic Restoration System is
in the Ready state
Or Loop Restoration is in the Ready state
Hot Line Tag Indicator
The HOT LINE TAG indicator (amber LED) shows status
of hot line tags.
Off:
All hot line tags have been removed
Flashes for ½ second every 2 seconds:
Hot line tag has been applied
Figure 33. HOT LINE TAG and STATUS indicators are located
on the face of the protection and control module.

Other manuals for S&C IntelliRupter PulseCloser

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C IntelliRupter PulseCloser and is the answer not in the manual?

S&C IntelliRupter PulseCloser Specifications

General IconGeneral
BrandS&C
ModelIntelliRupter PulseCloser
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals