22 S&C Instruction Sheet 681-510
Operation
Upper front panel
(not shown)
Termination
compartment
Operation compartment
Front panel
Padlock
Figure 44. Secure the enclosure. Make sure the operation
compartment and termination compartments are both closed
and padlocked.
Returning Equipment to Service
STEP 1. Make sure the load-interrupter switch and fault-
interrupter grounding means are removed.
STEP 2. Make certain the load-interrupter switches and
fault interrupters are in the correct positions
(Open or Closed).
STEP 3. If a pad-mounted enclosure is furnished, close
and padlock the termination compart ment
before energizing the circuit and operating any
switching devices. See Figure 44.
STEP 4. Padlock the switchgear before leaving the site
even momentarily. Observe this proce dure even
in those cases where the gear is accessible only
to quali ed persons.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the S&C Vista Series and is the answer not in the manual?

S&C Vista Series Specifications

General IconGeneral
Voltage RatingUp to 38 kV
Continuous Current600 A
Frequency60 Hz
Interrupting RatingUp to 25 kA
Interrupting Current20 kA, 25 kA
BIL95 kV, 125 kV, 150 kV
Insulation MediumSF6
Enclosure TypeMetal-clad or Metal-enclosed
Number of Ways2, 3, 4, 5, or 6
Switching MechanismVacuum Interrupters
Operating MechanismManual
Standards ComplianceIEEE C37.60
Fault InterruptionYes