S&C Instruction Sheet 682-510 13
Operation
Figure 15� Rotate the operation selector out of the way
Figure 14� The operation selector In the far right position
STEP 2
Remove the electrical-operation mechanical
blocking key from the motor operator. Verify the
operation selector is in the far right posi tion. This
allows operation between Closed and Open posi-
tions (see Figure 14) and prevents inad vertent
operation directly from the Closed position to/
from the Grounded position.
STEP 3� If the operation selector is blocking operation,
remove the electrical-operation mechanical
blocking key from the motor operator and rotate
the operation selector out of the way, as shown
in Figure 15.
Figure 13� Confirm the blade positions�
WARNING
ALWAYS confirm the position of switches or fault
interrupters by VISUALLY OBSERVING blade position�
Failure to follow this precaution can result in an
injury or equipment damage
WARNING
G-6694 SIDE 1
ALWAYS confirm the position of switches or fault interrupters by
VISUALLY OBSERVING blade position.
See Other Side for Phasing Instructions
CLOSED OPEN GROUNDED
Operation selector