14 S&C Instruction Sheet 682-510
Operation
STEP 4�
In the far left position, the operation selector
allows operation between the Open and
Grounded positions. See Figure 16. The opera-
tion selector in this position prevents inadvertent
manual operation directly from the Grounded
position to the Closed position.
STEP 5�
Insert the manual operating handle into the notch
of the motor operator operating mecha nism, as
shown in Figure 17.
STEP 6�
Rotate the manual operating handle in the
appropriate direction to open, close, or ground
the load-interrupter switch or three-pole fault
interrupter. Operation to the Open position is
shown in Figure 18.
Figure 17� Insert the manual operating handle�
Figure 18� Rotate the manual operating handle�
Manual operating handle
Operating mechanism
Recharge line
Figure 16� The operation selector in the far left position�