SEC3002 FIRE ALARM CONTROL PANEL
Page 22 of 24
Problem: the F.P.E.Out, the F.A.Out, or the S.C.Out is reported fault.
Possible reason and solution: ensure that a 4K7 EOL resistor is well connected to each of the
three ports; Check if the corresponding fuse of F2, F3 or F4 on the IO board blows out; Check
if the jumper of JP3, JP6 or JP10 beside the fuse is slipped over the pins accordingly.
Problem: no indication is given by the ZCP when there is a zonal fire, zonal fault, etc.
Possible reason and solution: the setup for ZCP is not registered; The ZCP circuit board is
disconnected or damaged; Check the ZCP board and register under the ZCP setup window.
Problem: a printer communication fault is reported.
Possible reason and solution: check if the cable between the printer and the B-Board is
connected or not; The printer may be powered off by pressing the SEL button on it that the
indicator is off.