SEC3002 FIRE ALARM CONTROL PANEL
Page 7 of 24
3.6 Other terminal connections
1. F.A. Out short for Fire Alarm Output: When there is a general fire the output is activated. A
4K7 end-of-line resistor (provided) is connected at the end of the circuit to allow the wiring to
be monitored. If the circuit is unused, the 4K7 resistor must still be connected. A typical
connection is shown below.
2. Fault Out short for Fault Output: The NO and COM are closed in normal state. When there
is a general fault, this voltage free relay switches.
3. F.P.E. Out short for Fire Protection Equipment Output: When there is a general fire the
output is activated by default. It can be disabled, therefore no output under disabled state. It