43
8-4. Outdoor Fan Speed Control (CL×××× models only)
Low ambient fan speed control
This function protects the compressor from being damaged due to flowback of the liquid refrigerant to the
compressor when the outdoor temperature is very low.
When the air temp. thermistor (TH) on the outdoor units detects a change in temperature, the controller on
the electrical component box activates to control the fanspeed automatically.
If the outdoor temperature falls below 57°F, the fan speed switches to MED.
If the outdoor temperature falls below 30°F, the fan speed switches to LOW.
*1 Regardless of outdoor temperature, outdoor fan motor operates at first at HIGH speed for
23 ± 5 seconds to give the motor an initial boost.
*2 When the fan speed switches, the controller terminal’s location where line voltage comes
out () shifts accordingly.
57°F
30°F
Outdoor
temperature
Fan speed
*
1
Fan motor output
*
2
(Line voltage 115V or 230V)
HIGH
MEDIUM
LOW
(BLU–GRY) or (WHT–GRY)
(VLT–GRY)
(YEL–GRY)
000-215 SM (1-56) 7/5/00 2:49 PM Page 43