9-3-3. Only compressor does not run
9-3-4. Only flap motor does not run
9-3-5. Function of outdoor fan speed control does not work properly.
(CLxx5x models only)
Measure resistance of
compressor motor winding.
Measure power supply
voltage.
The voltage is too low.
NO
Check compressor motor
capacitor.
Either internal protector or
overload relay is working.
Temperature of compressor
is abnormally high.
YES
YES
YES
NO
Refrigerant gas shortage. Charge refrigerant gas (R22).
Rotor may be locked up.
Measure resistance of flap
motor winding. (FLP)
• Check controller in outdoor unit.
(POW-CL125)
• Check outdoor air thermister in
outdoor unit.
(TH)
Refer to 8-4 "Outdoor Fan Speed Control."
000-215 SM (1-56) 7/5/00 2:49 PM Page 50