I-97
SM831148
1. Specifications
1
2
3
4
5
6
Reference diagram for snow-proof vents - 2
Space requirements for setting - (2)
C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U
Min. 11-13/36
Min. 11-13/16
Min. 39-3/8 Min. 7-7/8
Min. 59-1/16 Min. 78-3/4
Q
Min. 11-13/16
Min. 39-3/8
Min. 7-7/8
Q
Q
Min. P
Min. O
(1) Single-unit installation
(2) Obstacles on both sides
[Installation in front-rear rows]
[Obstacles to the front and rear of unit]
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 19-11/16 in. or more.
Dimension Q
If a snow protection duct is
attached after the unit is
installed, verify that dimension
Q is 19-11/16 in. or more.
The top and both sides must remain open. Either the obstacle to the front or the obstacle
to the rear must be no taller than the height of the outdoor unit.
The top and both sides must remain open. Either the obstacle to the front or
the obstacle to the rear must be no taller than the height of the outdoor unit.
Outdoor unit
O
39-3/8
C(H)2672R / 3072R /
3672R / 4272R
P
5-29/32
Unit: inch