EasyManua.ls Logo

Sanyo C4272R - Unit Specifications; Section 1: SPECIFICATIONS; Wall-Mounted Type

Sanyo C4272R
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
2
3
4
5
6
I-2
SM831148
1. Specifications
1-1 Unit Specifications
Wall-Mounted Type
Indoor Unit KHH2672R
Outdoor Unit CH2672R
POWER SOURCE
230 - 208 V / 1 Phase / 60 Hz
PERFORMANCE
Cooling Heating
Capacity * [minimum~muximum] BTU / h 23,000 [9,500~23,000] 27,600 [8,000~27,600]
(17˚F)** BTU / h 18,500
Moisture removal (High) Pints / h 7.4
Air circulation (H / M / L) 230 V CFM 540 / 460 / 380
External Static Pressure
in. WG
S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.9 10.3
ELECTRICAL RATINGS
Voltage rating V 230 208 230 208
Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes* (Without Back-up Heater)
A 14.0 15.5 14.6 16.1
Power input W 2,610 2,610 2,720 2,720
(17˚F)** W 2,160 2,160
Back-up Heater kW 1.8 1.47
Maximum overcurrent protection (Indoor/Outdoor)
A 15 / 30
Controls
Microprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor 3 and Automatic control / Variable
Optional Wired Remote Controller
RCS-SH80UG / RCS-TM80BG
Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
/ Automatic (Vertical )
Air filter Washable
Drain pump (Drain connection) (20A , OD26mm)
Compressor Rotary(SANYO)
Operation sound
Indoor - Hi/Me/Lo
dB - A 45 / 42 / 40
Outdoor - Hi dB - A 49
Refrigerant control
Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50)
Limit of tubing length at shipment ft. (m) 10~100 (3~30)
Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30)
between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35)
outer diameter Wide tube in. (mm) 5 / 8 (15.88)
Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 14- 9/16 (370) 30- 23/32 (780)
Width in. (mm) 49- 7/32 (1,250) 37 (940)
Depth in. (mm) 8- 9/32 (210) 13- 3/8 (340)
Package dimensions Indoor unit Outdoor unit
Height in. (mm) 18- 7/16 (468) 34- 31/32 (888)
Width in. (mm) 52- 23/32 (1,339) 39- 31/32 (1,015)
Depth in. (mm) 11- 3/8 (289) 16- 3/32 (409)
Net weight lbs. (kg) 44.1 (20) 128 (58)
Shipping weight lbs. (kg) 59.5 (27) 148 (67)
Shipping volume cu.ft. (m 3 ) 6.4 (0.181) 13.0 (0.369)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
FEATURES
MODEL No.
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

Table of Contents

Related product manuals