1
2
3
4
5
6
I-9
SM831148
1. Specifications
1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
Indoor Unit XH2672R
Outdoor Unit CH2672R
POWER SOURCE
230 - 208 V / 1 Phase / 60 Hz
PERFORMANCE
Cooling Heating
Capacity * [minimum~muximum] BTU / h 24,800 [9,500~24,800] 29,800 [8,000~29,800]
(17˚F)** BTU / h 18,300
Moisture removal (High) Pints / h 8.1
Air circulation (H / M / L) 230 V CFM 710 / 530 / 450
External Static Pressure
in. WG
S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.1 10.5
ELECTRICAL RATINGS
Voltage rating V 230 208 230 208
Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes*
A 15.6 17.3 14.8 16.4
Power input W 2,920 2,920 2,790 2,790
(17˚F)** W 2,200 2,200
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
A 15 / 30
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor 3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote Controller
RCS-SH80UA.WL / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical ) / Automatic (Vertical )
Air filter Washable, long life (2,500 hr)
Drain pump (Drain connection)
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Compressor Rotary(SANYO)
Operation sound
Indoor - Hi/Me/Lo
dB - A 38 / 35 / 31
Outdoor - Hi dB - A 49
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50)
Limit of tubing length at shipment ft. (m) 10~100 (3~30)
Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30)
between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35)
outer diameter Wide tube in. (mm) 5 / 8 (15.88)
Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Indoor unit (Include panel) Outdoor unit
Unit dimensions Height in. (mm) 13-5/16 (338) 30- 23/32 (780)
Width in. (mm) 33-55/64 (860) 37 (940)
Depth in. (mm) 33-55/64 (860) 13- 3/8 (340)
Package dimensions Body Panel Outdoor unit
Height in. (mm) 11-9/64 (283) 4-3/32 (104) 34- 31/32 (888)
Width in. (mm) 32-7/8 (835) 37-61/64 (964) 39- 31/32 (1,015)
Depth in. (mm) 33-9/32 (845) 39-21/64 (999) 16- 3/32 (409)
Net weight lbs. (kg) 49 (22) 11 (5) 128 (58)
Shipping weight lbs. (kg) 57 (26) 18 (8) 148 (67)
Shipping volume cu.ft. (m 3 ) 7.1 (0.200) 3.6 (0.100) 13.0 (0.369)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
FEATURES
MODEL No.
Controls Microprocessor
RCS-SH80UG / RCS-TM80BG