1
2
3
4
5
6
I-26
SM831148
1. Specifications
1-1 Unit Specifications
Ceiling-Mounted Type
Indoor Unit TH4272R
Outdoor Unit C4272R
POWER SOURCE
230 - 208 V / 1 Phase / 60 Hz
PERFORMANCE
Cooling
Capacity * [minimum~muximum] BTU / h 39,000 [9,500~39,000]
(17˚F)** BTU / h
Moisture removal (High) Pints / h 12.6
Air circulation (H / M / L) 230 V CFM 1100 / 930 / 750
External Static Pressure
in. WG
S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.6
ELECTRICAL RATINGS
Voltage rating V 230 208
Available voltage range V VAC 187 - 253
Max. Running amperes* A 21.1 23.3
Power input W 4,140 4,140
(17˚F)**
W
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
A 15 / 40
Controls Microprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor 3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
/ Automatic (Vertical )
Air filter Washable, long life (2,500 hr)
Drain pump (Drain connection) (20A , OD26mm)
Compressor Rotary(SANYO)
Operation sound
Indoor - Hi/Me/Lo
dB - A 44 / 41 / 37
Outdoor - Hi dB - A 53
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50)
Limit of tubing length at shipment ft. (m) 10~100 (3~30)
Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30)
between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35)
outer diameter Wide tube in. (mm) 5 / 8 (15.88)
Refrigerant amount at shipment lbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 9-7/16 (240) 48-7/16 (1,230 )
Width in. (mm) 62-1/32 (1,575) 37 (940)
Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Package dimensions Indoor unit Outdoor unit
Height in. (mm) 12-15/32 (317) 52-3/8 (1,330 )
Width in. (mm) 66-1/16 (1,678) 39- 31/32 (1,015)
Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
Net weight lbs. (kg) 84 (38) 220 (100)
Shipping weight lbs. (kg) 97 (44) 240 (109 )
Shipping volume cu.ft. (m 3 ) 14.8 (0.420) 19.5 (0.552 )
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
FEATURES
MODEL No.
RCS-SH80UG / RCS-TM80BG
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB