3 - 7
Trouble Diagnosis
3. W-3WAY ECO-i Alarm Codes
1
2
3
4
5
6
7
8
E16 Alarm
Alarm code E16
Alarm meaning Automatic address setting alarm (too many units)
Alarm conditions
There were a number of indoor units was too many when Automatic address setting was performed.
After initial communications were completed, an unrecognized unit was detected.
Probable cause
(1) The SW for setting the number of indoor units is incorrect.
(2) The inter-unit control wiring is wired incorrectly.
Check (1)
Refer to the test run servicing materials and check the number of indoor units that is set.
(2) Check the inter-unit control wiring at the indoor and outdoor units.
Correction After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic
address setting again.
Example
Notes
E20 Alarm
Alarm code E20
Alarm meaning No indoor units at automatic address setting.
Alarm conditions When automatic address setting was performed, no indoor units were recognized.
Probable cause (1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut.
(2) Serial connector (OC: CN001) is disconnected at the outdoor unit.
(3) The power is OFF at all indoor units in the system.
Check (1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.
(2) Check whether serial connector (OC: CN001) is disconnected at the outdoor unit.
(3) Check the power at the indoor units.
Correction (1)
Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.
Example
Notes Position of serial connector (OC: CN001) on W-3WAY control PCB
E24 Alarm
Alarm code E24
Alarm meaning Outdoor unit (main) failed to receive signal from other outdoor unit (sub).
Alarm conditions After initial communications were completed, communications from an outdoor unit stopped.
Probable cause (1) After initial communications were completed, the outdoor unit main/sub control wiring was cut.
(2) After initial communications were completed, the outdoor unit power was turned OFF.
Check
Correction
Example
Notes
CN001