31
Indoor Unit SAPK241GJA SAPK241MBA
Outdoor Unit SAPC241GA SAPC241MA
240V Single Phase 50Hz
RATING CAPACITY 6.45 kW
AIR FLOW RATE 830
m
3
/h
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 30 35 40 45 50
TC 5.93 5.65 5.31 4.89 4.40
CM 2.25 2.42 2.68 2.95 3.21
21 SHC 3.84 3.68 3.49 3.26 3.01
15 23 SHC 4.22 4.06 3.87 3.64 3.39
25 SHC 4.60 4.44 4.25 4.02 3.77
27 SHC 4.98 4.82 4.63 4.40 4.15
29 SHC 5.36 5.20 5.01 4.78 4.40
31 SHC 5.75 5.58 5.31 4.89 4.40
TC 6.37 6.06 5.70 5.24 4.73
CM 2.32 2.49 2.75 3.02 3.28
21 SHC 3.46 3.29 3.10 2.87 2.62
17 23 SHC 3.84 3.67 3.48 3.25 3.00
25 SHC 4.22 4.06 3.86 3.63 3.38
27 SHC 4.60 4.44 4.24 4.01 3.76
29 SHC 4.98 4.82 4.62 4.39 4.14
31 SHC 5.36 5.20 5.00 4.77 4.52
TC 6.77 # 6.45 6.06 5.58 5.03
CM 2.39 2.56 2.83 3.10 3.37
21 SHC 3.04 2.88 2.69 2.46 2.21
19 23 SHC 3.42 3.26 3.07 2.84 2.59
25 SHC 3.80 3.64 3.45 3.22 2.97
27 SHC 4.18 4.02 3.83 3.60 3.35
29 SHC 4.56 4.40 4.21 3.98 3.73
31 SHC 4.94 4.78 4.59 4.36 4.11
TC 7.18 6.84 6.43 5.91 5.33
CM 2.45 2.63 2.91 3.18 3.46
23 SHC 3.00 2.83 2.64 2.42 2.17
21 25 SHC 3.38 3.21 3.02 2.80 2.55
27 SHC 3.76 3.59 3.41 3.18 2.93
29 SHC 4.14 3.97 3.79 3.56 3.31
31 SHC 4.52 4.35 4.17 3.94 3.69
TC 7.60 7.18 6.72 6.25 5.66
CM 2.52 2.70 2.98 3.26 3.54
23 25 SHC 2.91 2.73 2.54 2.34 2.11
27 SHC 3.29 3.11 2.92 2.72 2.49
29 SHC 3.67 3.49 3.30 3.10 2.87
31 SHC 4.06 3.87 3.68 3.48 3.25
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.