7. ELECTRICAL DATA
7-1. Electrical Characteristics
1 - indoor unit in operation
2 - indoor units in operation
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 240V Single phase 50Hz
Rating Conditions Running Amps. A 0.36 0.50 8.44 9.3
Power Input kW 0.080 0.119 1.921 2.12
Full Load Conditions Running Amps. A 0.36 0.50 10.04 10.9
Power Input kW 0.080 0.119 2.261 2.46
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAPK91A (
2)
Outdoor Unit SAPCM1821A
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 240V Single phase 50Hz
Rating Conditions Running Amps. A 0.18 0.50 4.32 5.0
Power Input kW 0.040 0.119 0.951 1.11
Full Load Conditions Running Amps. A 0.18 0.50 5.12 5.8
Power Input kW 0.040 0.119 1.121 1.28
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAPK91A (
1)
Outdoor Unit SAPCM1821A
12