27
Indoor Unit SAPK122A
Outdoor Unit SAPC122A
240V Single Phase 50Hz
RATING CAPACITY 3.40 kW
AIR FLOW RATE 470
m
3
/h
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 30 35 40 43
TC 3.13 2.98 2.80 2.58
CM 1.05 1.13 1.22 1.36
21 SHC 2.06 1.98 1.88 1.77
15 23 SHC 2.29 2.20 2.11 1.99
25 SHC 2.51 2.43 2.33 2.22
27 SHC 2.74 2.65 2.56 2.44
29 SHC 2.96 2.88 2.78 2.58
31 SHC 3.13 2.98 2.80 2.58
TC 3.36 3.20 3.00 2.76
CM 1.08 1.16 1.26 1.39
21 SHC 1.83 1.75 1.65 1.54
17 23 SHC 2.06 1.97 1.88 1.76
25 SHC 2.28 2.20 2.10 1.99
27 SHC 2.51 2.42 2.33 2.21
29 SHC 2.73 2.65 2.55 2.44
31 SHC 2.96 2.87 2.78 2.66
TC 3.57 # 3.40 3.20 2.94
CM 1.11 1.19 1.30 1.43
21 SHC 1.59 1.50 1.41 1.29
19 23 SHC 1.81 1.73 1.63 1.52
25 SHC 2.04 1.95 1.86 1.74
27 SHC 2.26 2.18 2.08 1.97
29 SHC 2.49 2.41 2.31 2.19
31 SHC 2.71 2.63 2.54 2.42
TC 3.78 3.60 3.39 3.12
CM 1.14 1.23 1.33 1.47
23 SHC 1.56 1.48 1.39 1.27
21 25 SHC 1.79 1.71 1.61 1.50
27 SHC 2.01 1.93 1.84 1.72
29 SHC 2.24 2.16 2.06 1.95
31 SHC 2.46 2.38 2.29 2.17
TC 4.01 3.78 3.54 3.29
CM 1.17 1.26 1.37 1.50
23 25 SHC 1.52 1.43 1.33 1.23
27 SHC 1.74 1.65 1.55 1.46
29 SHC 1.97 1.88 1.78 1.68
31 SHC 2.19 2.10 2.01 1.91
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.