9. TROUBLESHOOTING
9-1. Check before and after troubleshooting
9-1-1. Check power supply wiring.
Check that power supply wires are connected to correct terminals on the terminal plate in the outdoor unit.
9-1-2. Check inter-unit wiring.
Check that inter-unit wiring is correctly connected to the indoor unit from the outdoor unit.
9-1-3. Check power supply.
Check that voltage is in specified range (±10% of the rating).
Check that power is being supplied.
9-1-4. Check lead wires and connectors in indoor and outdoor units.
Check that coating of lead wires is not damaged.
Check that lead wires and connectors are firmly connected.
Check that wiring is correct.
Grounding
line
OUTDOOR UNITINDOOR UNIT
1
2
4
1
2
4
5
5
Power line
5P
Terminal
5P
Terminal
Grounding line
INDOOR UNIT OUTDOOR UNIT
TerminalTerminal
Power
line
Control
line
1
4
2
1
4
2
5
6
Grounding line
Power supply
50 Hz, 1-phase,
220-240 VAC
Grounding line
• K182A + C182A
• K252A + C252A
Inter-unit
wiring
Inter-unit
wiring
Power supply
50 Hz, 1-phase ,
220-240 VAC
• K92A + C92A
• K122A + C122A
43
WARNING
Hazardous voltage can cause ELECTRIC SHOCK or
DEATH. Disconnect power or turn off circuit breaker
before you start checking or servicing.