EasyManua.ls Logo

Sanyo SPW-CR903GV8 - Page 106

Sanyo SPW-CR903GV8
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I - 101
SM830063
1
ECO MULTI SYSTEM Unit Specifications
MODEL No. Indoor Unit SPW-DR363GH56
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 10.6 11.4
BTU / h 36,000 39,000
Air circulation (Hi / Me / Lo) m
3
/ h 1,800 / 1,680 / 1,500
External static pressure (High) mmAq (Pa) 18 (176)
Moisture removal (High) Liters / h 4.4
ELECTRICAL RATINGS
Voltage rating V 220 - 230 - 240
Available voltage range V 198 – 264
Running amperes A 2.46 - 2.46 - 2.47 2.46 - 2.46 - 2.47
Power input W 520 - 545 - 570 520 - 545 - 570
Power factor % 96 - 96 - 96 96 - 96 - 96
Fan motor locked rotor amperes A 4 - 4 - 4
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air filter Field supply
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 45 / 44 / 42
Refrigerant tubing connections Flare type
Refrigerant tube Narrow tube mm (in) 9.52 (3 / 8)
diameter Wide tube mm (in) 19.05 (3 / 4)
Drain connection 20 A, OD26 mm
Remote Controller Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories Optional /
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Dimensions Height mm (in) 420 (16 - 1 / 2) 513 (20 - 1 / 4)
Width mm (in) 1,065 (41 - 7 / 8) 1,148 (45 - 1 / 4)
Depth mm (in) 620 (24 - 3 / 8) 713 ( 28 - 1 / 8)
Net weight kg (lb) 50 ( 110 )
Shipping weight kg (lb) 64 ( 141 )
Shipping volume m
3
(cu. ft) 0.42 ( 14.8 )
Unit specifications (B)
8. Concealed Duct High Static Pressure Type
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Heating: Indoor air temperature 20 °C DB , Outdoor air temperature 7 °CDB/6 °CWB

Table of Contents