I - 114
SM830063
ECO MULTI SYSTEM Unit Specifications
1
9-2. Major component specifications
Indoor unit (A)
MODEL No. SPW-FR93GH56
Source 220 - 230 - 240 V / 1 phase / 50Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (1 … ø 153)
Fan motor
Model…Nominal output W KFT6Q-11A3P … 15 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 6 … 831
Coil resistance BRN WHT : 370.2 ORG YEL : 168.0
(Ambient temperature 20°C) WHT VLT : 105.4 YEL PNK : 92.16
VLT ORG : 67.05
Safety device
Operating temperature Open °C 130 ± 5
Close °C (115 ± 5)
Run capacitor VAC, µF 440 V, 1.0 µF
Electronic expansion valve
Coil DKV-MOZS550E0
Coil resistance (at 20°C) ORG GRY : 46 , YEL GRY : 46
RED GRY : 46 , BLK GRY : 46
Valve body IKV-24D12
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 3 … 2.0
Face area m
2
0.102
9. Floor-Standing Type (F Type)