I - 100
SM830063
ECO MULTI SYSTEM Unit Specifications
1
8. Concealed Duct High Static Pressure Type
8-1. Specification
Unit specifications (A)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Heating: Indoor air temperature 20 °C DB , Outdoor air temperature 7 °CDB/6 °CWB
*
Use the “Tube connector” (accessory part with unit).
MODEL No. Indoor Unit SPW-DR253GH56
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 7.3 8.0
BTU / h 25,000 27,000
Air circulation (Hi / Me / Lo) m
3
/ h 1,380 / 1,320 / 1,260
External static pressure (High) mmAq (Pa) 19 (186)
Moisture removal (High) Liters / h 3.1 —
ELECTRICAL RATINGS
Voltage rating V 220 - 230 - 240
Available voltage range V 198 – 264
Running amperes A 2.29 - 2.30 - 2.31 2.29 - 2.30 - 2.31
Power input W 480 - 505 - 530 480 - 505 - 530
Power factor % 95 - 95 - 96 95 - 95 - 96
Fan motor locked rotor amperes A 3 - 3 - 3
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air filter Field supply
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 44 / 43 / 42
Refrigerant tubing connections Flare type
Refrigerant tube Narrow tube mm (in) 9.52 (3 / 8)
*
diameter Wide tube mm (in) 15.88 (5 / 8)
Drain connection 20 A, OD26 mm
Remote Controller Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories Optional / —
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Dimensions Height mm (in) 420 (16 - 1 / 2) 513 (20 - 1 / 4)
Width mm (in) 1,065 ( 41 - 7 / 8) 1,148 (45 - 1 / 4)
Depth mm (in) 620 (24 - 3 / 8) 713 (28 - 1 / 8)
Net weight kg (lb) 47 ( 104 )
Shipping weight kg (lb) 61 ( 134 )
Shipping volume m
3
(cu. ft) 0.42 ( 14.8 )