I - 105
SM830063
1
ECO MULTI SYSTEM Unit Specifications
Indoor unit (C)
MODEL No. SPW-DR483GH56
Source 220 - 230 - 240 V / 1 phase / 50Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (1 … ø 250)
Fan motor
Model…Nominal output W KFC4Q-401A5P … 400 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,077
Coil resistance BRN WHT : 11.05 ORG YEL : 4.57
(Ambient temperature 20°C) WHT VLT : 1.80 YEL PNK : 7.70
VLT ORG : 1.00
Safety device
Operating temperature Open °C 130 ± 5
Close °C (79 ± 15)
Run capacitor VAC, µF 440 V, 7 µF x 2
Electronic expansion valve
Coil EKV-MOZS559E0
Coil resistance (at 20°C) ORG GRY : 46 , YEL GRY : 46
RED GRY : 46 , BLK GRY : 46
Valve body HKV-30D16
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 4 … 2.0
Face area m
2
0.273
8. Concealed Duct High Static Pressure Type