ECO MULTI SYSTEM Unit Specifications
SM830063
I-72
1
6. Ceiling Mounted Type
MODEL No. Indoor Unit SPW-TR483GH56
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 14.0 16.0
BTU / h 47,800 54,600
Air circulation (Hi / Me / Lo) m
3
/ h 1,920 / 1,680 / 1,320
Moisture removal (High) Liters / h 7.0 —
ELECTRICAL RATINGS
Voltage rating V 220 - 230 - 240
Available voltage range V 198 – 264
Running amperes A 0.95 - 0.96 - 0.98 0.86 - 0.88 - 0.90
Power input W 200 - 210 - 220 180 - 190 - 200
Power factor % 96 - 95 - 94 95 - 94 - 93
Fan motor locked rotor amperes A 2 - 2 - 2
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds (Indoor unit) 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 44 / 41 / 37
Refrigerant tubing connections Flare type
Refrigerant tube Narrow tube mm (in) 9.52 (3 / 8)
diameter Wide tube mm (in) 19.05 (3 / 4)
Drain connection 20 A, OD26 mm
Remote Controller Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories Optional / —
Color (Approximate value) Munsell 10Y9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Dimensions Height mm (in) 240 ( 9 - 7 /16) 317 (12 - 15 /32)
Width mm (in) 1,575 (62 ) 1,678 (66 - 1 /16)
Depth mm (in) 670 (26 - 3 / 8) 789 (31 - 1 /16)
Net weight kg (lb) 38 ( 84 )
Shipping weight kg (lb) 44 ( 97 )
Shipping volume m
3
(cu. ft) 0.42 ( 14.8 )
Unit specifications (D)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Heating: Indoor air temperature 20 °C DB , Outdoor air temperature 7 °CDB/6 °CWB