I-83
SM830063
1
ECO MULTI SYSTEM Unit Specifications
MODEL No. Indoor Unit SPW-UR183GH56
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 5.6 6.3
BTU / h 19,000 21,000
Air circulation (Hi / Me / Lo) m
3
/ h 840 / 680 / 540
External static pressure (High) mmAq (Pa) 5 (49): at shipment, 10 (98): using the booster cable
Moisture removal (High) Liters / h 2.7 —
ELECTRICAL RATINGS
Voltage rating V 220 - 230 - 240
Available voltage range V 198 – 264
Running amperes A 0.56 - 0.56 - 0.56 0.56 - 0.56 - 0.56
Power input W 120 - 125 - 130 120 - 125 - 130
Power factor % 97 - 97 - 97 97 - 97 - 97
Fan motor locked rotor amperes A 1 - 1 - 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air filter Field supply
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 34 / 30 / 26
using the booster cable (Hi / Me / Lo)
dB-A 39 / 36 / 32
Refrigerant tubing connections Flare type
Refrigerant tube Narrow tube mm (in) 9.52 (3 / 8)
diameter Wide tube mm (in) 15.88 (5 / 8)
Drain connection 25 A, OD32 mm
Drain pump Max. head 25 cm above drain connection
Remote Controller Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories Optional / Booster cable
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Dimensions Height mm (in) 310 (12 - 1 / 4) 380 (15 - )
Width mm (in) 750 (29 - 17 / 32) 949 (37 - 3 / 8)
Depth mm (in) 665 (26 - 1 / 4) 866 ( 34 - 1 /16)
Net weight kg (lb) 32 ( 71 )
Shipping weight kg (lb) 38 ( 84 )
Shipping volume m
3
(cu. ft) 0.312 ( 11.0 )
Unit specifications (C)
7. Concealed Duct Type
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Heating: Indoor air temperature 20 °C DB , Outdoor air temperature 7 °CDB/6 °CWB