ECO MULTI SYSTEM Unit Spesifications
SM830063
I-4
1
1. Outdoor Unit
Unit specifications (B)
MODEL No. Outdoor Unit SPW – CR363GV8
POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz
PERFORMANCE Cooling
Capacity kW 11.2
BTU / h 38,200
Air circulation (Hi) m
3
/min(cu. ft/min) 84 (2,970)
ELECTRICAL RATINGS
Voltage rating V 380 400 415
Available voltage range V 342 - 456
Running amperes A 7.9 7.9 7.9
Max. running amperes* A 9.0 8.9 8.7
Power input kW 4.62 4.60 4.64
Max. power input* kW 5.22 5.18 5.13
Power factor % 89 84 82
C.O.P W/W 2.42 2.43 2.41
Compressor locked rotor amperes A 51 53 55
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment kg R407C - 3.4
Refrigerant control Electronic expansion valve
Operation sound (Hi) dB-A 55
External finish Galvanized steel plate with powder paint
Color (Approximate value) Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length m(ft.) 70 (230)
Limit of elevation difference m(ft.) Outdoor unit is higher than indoor unit : 40 (131)
between the two units Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube Narrow tube mm (in) 9.52 ( 3 / 8 )
outer diameter Wide tube mm (in) 19.05 ( 3 / 4 )
Refrigerant tubing kit / joint kit Optional
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Unit dimensions Height mm(in) 1,235 (48 - 20 /32) 1,326 (52 - 7 / 32)
Width mm(in) 940 (37 ) 1,016 (40 )
Depth mm(in) 340 (13 - 12 /32) 416 (16 - 12 / 32)
Net weight kg(lb) 118 ( 260 )
Shipping weight kg(lb) 125 ( 276 )
Shipping volume m
3
(Cu. ft.) 0.56 ( 19.8 )
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °C DB / 19.0 °C WB , Outdoor air temperature 35 °C DB
* Full load conditions at Indoor / outdoor capacity ratio 100 %
Cooling: Indoor air temperature 32 °C DB / 22.5 °C WB , Outdoor air temperature 43 °C DB / 25.5 °C WB