13
2H/1C Heat Pump (with auxiliary heat) 3H/2C Heat Pump (with auxiliary heat)
1 Power supply
2 Remove jumper for 2-transformer system
3 Optional 24VAC common connection
4 Common connection must come from cooling transformer
5 If L terminal is used, 24VAC common (terminal C) must be connected
6 Install field jumper between Aux and E terminals if there is no emergency heat relay
L
Equipment monitor
5
RC
Power 1
RH
(RH+RC joined by jumper)
Y
Compressor relay
E
Emergency heat relay
6
Aux
Auxiliary heat relay (Heat 2)
6
O/B,O:
Changeover valve energized in heating
B:
Changeover valve energized in cooling
G
Fan relay
C
24VAC common
S1/S2
Remote sensor
L
Equipment monitor
5
RC
Power
1
RH
(RH+RC joined by jumper)
Y
Compressor relay
E
Emergency heat relay 6
Aux
Auxiliary heat relay (Heat 2)
6
O/B,O:
Changeover valve energized in heating
B:
Changeover valve energized in cooling
Y2
Compressor relay 2
G
Fan relay
C
24VAC common
S1/S2
Remote sensor