Select OF to deactivate the intelligent recovery function. Intelligent recovery function doesn’t activate when program
setting to non-programmable.
7.First heating cycle rate
FA: Fast rate, heating will activate 0.6℉ below set point
SL: Slow rate, heating will activate 1.2℉ below set point
8.First cooling cycle rate
FA: Fast rate, cooling will activate 1.2℉above set point
SL: Slow rate, cooling will activate 1.7℉ above set point
9. Emergency heat cycle rate
This option apply only to HP1or HP2 setting in heating type option
FA: Fast rate, Emergency will activate 1.2 ℉ below set point
SL: Slow rate, Emergency heat will activate 1.7℉ below set point
10.Select compressor lockout delay
To protect the compressor from short cycling, you can select compressor off-time cycle between 0 or 5 minutes.
When the thermostat compressor time delay occurs, “Comp Dly” display during compressor lockout.
11.Select display backlight
The display backlight improves display contrast in low lighting conditions.
Select 1 for NO backlight display. Select 2 for the backlight to come on for approximately 30 seconds when any button
of the thermostat is touched. Select 3 for the backlight to remain on continuously.
NOTE: When operated from batteries (No “C” terminal connection, or if AC power goes off), the LCD
continuously display of backlight will be disabled.)