13
(2) static relays contact ( power : 48Vdc / 100mA )
(option 6 relays)
COM contact commun
OUT 1 contact relay 1
OUT 2 contact relay 2
.
.
.
.
OUT 6 contact relay 6
(2) opto-insulated inputs
You must connect the input to the com with a contact and a power supply (12 to
24 VCC). The polarity of the power supply is free on the input / com .
COM COM
IN1 input 1
IN2 input 2
Analog output opto- insulated (0/10V and 4/20mA)
This analog output depends of the model (IPE50P 2S ANA only)
You must set the output you need through the menu An.out (paragraph 13)
Current (4/20mA) (max load : 300Ω)
I+ +
COM - -
Tension (0/10V) (min load : 10kΩ)
V+ +
COM - -
COM
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
48Vdc / 100mA