schwankgroup.com/schwankair
1. Recommended outlet air temperature for good comfort and optimized output.
2. Nominal output at given supply and return water temperature.
Model Nozzle
width x depth (in)
Max Velocity
at nozzle (fpm)
Outlet Velocity
(fpm)
Outlet Velocity Uniformity
(%)
AC-TA36-23 38.4x2.6 2346 1974 81
AC-TE36-20(48)(60) 38.4x2.6 2346 1974 81
AC-TA60-23 58.5x2.6 2267 1860 80
AC-TE60-20(48)(60) 58.5x2.6 2267 1860 80
AC-TA72-23 77.8X2.6 2346 1974 81
AC-TE72-20(48)(60) 77.8X2.6 2346 1974 81
AC-TW36-23 38.4x2.6 2165 1785 75
AC-TW60-23 58.5x2.6 1791 1545 82
AC-TW72-23 77.8X2.6 2165 1785 75
Model Fan
Speed
Airflow
(CFM)
Output
(MBH)
Return water
temp. (°F)
Water flow
(GPM)
Pressure
drop (kPa)
Output*
2
(MBH)
Outlet air
temp. (°F)
Water
flow (GPM)
Pressure
drop (kPa)
AC-TW36-23 max 1050 34.1 108 1.0 1.4 50.9 108 2.9 8.8
AC-TW60-23 max 1550 52.2 100 1.4 2.0 82.6 113 4.7 16.2
AC-TW72-23 max 2150 72.4 100 1.9 2.6 114.0 111 6.5 21.6
Technical Specification
Supply water temperature: 176 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F
*1
Water temperature: 176/140 °F
Room temperature: +64 °F
Model Fan
Speed
Airflow
(CFM)
Output
(MBH)
Return water
temp. (°F)
Water flow
(GPM)
Pressure drop
(kPa)
Output*
2
(MBH)
Outlet air
temp. (°F)
Water flow
(GPM)
Pressure drop
(kPa)
AC-TW36-23 max 1050 34.8 118 3.1 10.9 28.0 90 1.6 3.2
AC-TW60-23 max 1550 49.8 108 3.2 8.7 46.4 91 2.6 6.1
AC-TW72-23 max 2150 73.7 113 5.5 17.2 64.5 91 3.6 8.1
Supply water temperature: 140 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F
*1
Water temperature: 140/104 °F
Room temperature: +64 °F
AC TE 72 60
Select12 Series
Electric Heated
Air Curtain
Nominal Length of unit
in inch
Voltage Code 600V