2-46 Relay Element Settings
Date Code 20020206 SEL-300G Instruction Manual
The four available RTD types (Table 2-2 lists RTD resistance versus temperature for the RTD)
are:
• 100-ohm platinum (PT100)
• 100-ohm nickel (NI100)
• 120-ohm nickel (NI120)
• 10-ohm copper (CU10)
RTD Alarms & Trip Temperature Settings
Setting Prompt
Setting Range Setting Name = Factory Default
RTD Trip Temperature OFF, 32°–482°F TRTMP1 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP1 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP2 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP2 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP3 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP3 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP4 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP4 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP5 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP5 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP6 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP6 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP7 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP7 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP8 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP8 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP9 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP9 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP10 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP10 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP11 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP11 = OFF
RTD Trip Temperature OFF, 32°–482°F TRTMP12 = OFF
RTD Alarm Temperature OFF, 32°–482°F ALTMP12 = OFF
Enable Winding Trip Voting Y, N EWDGV = N