Configuration, Fast Meter, and Fast Operate Commands D-15
SEL-300G Instruction Manual Date Code 20001212
A5B9 Fast Meter Status Acknowledge Message
In response to the A5B9 request, the relay clears the Fast Meter (message A5D1) Status Byte.
The SEL-300G Status Byte contains one active bit, STSET (bit 4). The bit is set on power up
and on settings changes. If the STSET bit is set, the external device should request the A5C1,
A5C2, and A5C3 messages. The external device can then determine if the scale factors or line
configuration parameters have been modified.
A5CE Fast Operate Configuration Block
In response to the A5CE request, the relay sends the following block:
Data
Description
A5CE Command
3C Length
01 Support 1 circuit breaker
0010 Support 16 remote bit set/clear commands
01 Allow remote bit pulse commands
00 Reserved
31 Operate code, open breaker (OC1)
11 Operate code, close breaker (CC)
00 Operate code, clear remote bit RB1
20 Operate code, set remote bit RB1
40 Operate code, pulse remote bit RB1
01 Operate code, clear remote bit RB2
21 Operate code, set remote bit RB2
41 Operate code, pulse remote bit RB2
02 Operate code, clear remote bit RB3
22 Operate code, set remote bit RB3
42 Operate code, pulse remote bit RB3
03 Operate code, clear remote bit RB4
23 Operate code, set remote bit RB4
43 Operate code, pulse remote bit RB4
04 Operate code, clear remote bit RB5
24 Operate code, set remote bit RB5
44 Operate code, pulse remote bit RB5
05 Operate code, clear remote bit RB6
25 Operate code, set remote bit RB6
45 Operate code, pulse remote bit RB6
06 Operate code, clear remote bit RB7
26 Operate code, set remote bit RB7
46 Operate code, pulse remote bit RB7
07 Operate code, clear remote bit RB8
27 Operate code, set remote bit RB8
47 Operate code, pulse remote bit RB8
08 Operate code, clear remote bit RB9
28 Operate code, set remote bit RB9
48 Operate code, pulse remote bit RB9
09 Operate code, clear remote bit RB10