D-12 Compressed ASCII Commands
Date Code 20001212 SEL-300G Instruction Manual
In response to the A5D1 request, Model SEL-0300G3 Relays send the following block:
Data
Description
A5D1 Command
B4 Length
1-byte 1 Status Byte
112-bytes X and Y components of: IA, IB, IC, IN, VA, VB, VC, VS,
VN, IA87, IB87, IC87, Freq, and Vdc in 4-byte IEEE FPS
8-bytes Time stamp
54-bytes 54 Digital banks: TAR0 - TAR53
1-byte Reserved
checksum 1-byte checksum of all preceding bytes
A5C2/A5C3 Demand/Peak Demand Fast Meter Configuration Messages
In response to the A5C2 or A5C3 request, the relay sends the following block:
Data
Description
A5C2 or A5C3 Command; Demand (A5C2) or Peak Demand (A5C3)
EE Length
01 # of status flag bytes
00 Scale factors in meter message
00 # of scale factors
16 # of analog input channels
01 # of samples per channel
00 # of digital banks
00 # of calculation blocks
0004 Analog channel offset
00B4 Time stamp offset
FFFF Digital offset
494100000000 Analog channel name (IA)
02 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
494200000000 Analog channel name (IB)
02 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
494300000000 Analog channel name (IC)
02 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
494E00000000 Analog channel name (IN)
02 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
494700000000 Analog channel name (IG)
02 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message