Select Door Sense or Inhibit Input Default: Door Sense
The input (gray wire) can be programmed for DOOR SENSE or
INHIBIT.
Press: 1 0 # Input #
Input=0 for Door Sense; =1 for Inhibit
When programmed for DOOR SENSE, if an open condition on
the input occurs before access is granted (with an entry code or
with the request-to-enter input) a FORCED ENTRY output will
occur. If an open condition remains beyond the door ajar time
following a valid relay activation for access, a DOOR AJAR
output will occur.
When programmed for INHIBIT, a closed condition on the input
will prevent Relay #1 from activating when access is requested
with an entry code. This mode is typically used with an
external timer to disable the access device at certain times.
Select Forced Entry Output Default: No Output
Sets which output activates if the DOOR SENSE input opens
before authorized access is granted. This output is not timed.
The selected relay latches ON, until any valid code (timed or
toggled) is entered.
Press: 1 1 # Output #
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Door Ajar Output Default: No Output
Sets which output activates if the DOOR SENSE input stays
open beyond the door ajar time, after access is granted (door
ajar time is adjustable using Function 25 on next page). This
output is not timed. When the DOOR SENSE input returns to
normal, the output turns off.
Press: 1 2 # Output #
Output=Output to Activate (0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
ADDITIONAL PROGRAMMING OPTIONS
There are several 918 EntryCheck™ programming options. For
most installations, the basic programming on the previous page
is sufficient.
Erasing All Entry Codes
WARNING: PERFORMING THIS COMMAND WILL REMOVE
ALL ENTRY CODES FROM THE MEMORY. THE MASTER
CODE WILL NOT BE RESET.
Press: 9 7 # 0 0 0 0 0 0
# 0 0 0 0 0 0
#
Note: The green indicator will light while the memory is being erased.
This may take up to 15 seconds.
Select Keypad Active Output Default: No Output
Sets which output activates when any keys are pressed. This
output is timed. If toggle mode is selected for the output, the timer
value defaults to 2 seconds.
Press: 1 4 # Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Keypad Lockout Output Default: No Output
Sets which output activates when the keypad is “locked out” after
too many incorrect entry code attempts. The lockout time is 60
seconds.
Press: 1 3
# Output
#
Output=Output to Activate (0-4)
1=Main Relay; 2 = Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Alarm Shunt Output Default: No Output
Sets which output activates during the time access is granted.
(Use this output ot shunt alarm contacts attached to the access
door.) This output may be timed or toggled.
Press: 1 5 # Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Request-to-Exit Output Default: Main Output
Sets which output activates when the Request-to-Exit input is
grounded.
Press: 1 6 # Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Main Relay On-time Default: 2 Seconds
Sets the length of time the Main Relay activates when triggered.
Green LED is on when Main Relay is active.
Press: 2 1 # Seconds
#
Seconds=Output time in seconds (0-60)
Auxiliary Relay On-time Default: 2 Seconds
Sets the length of time the Auxiliary Relay activates when triggered.
Press: 2 2 # Seconds
#
Seconds=Output time in seconds (0-60)
Solid-state Output #3 On-time Default: 2 Seconds
Sets the length of time Output #3 activates when triggered.
Press: 2 3 # Seconds
#
Seconds=Output time in seconds (0-60)