GATE 1 DG R1
Sistemi Elettronici
di Apertura Porte e Cancelli
International registered trademark n. 804888
®
SEA S.p.A.
Zona industriale 64020 S.ATTO Teramo - (ITALY)
Tel. +39 0861 588341 r.a. Fax +39 0861 588344
www.seateam.com
seacom@seateam.com
67410182
Italiano
English
CENTRALE DI COMANDO PER CANCELLI SCORREVOLI, BATTENTI, BARRIERE E PORTE DA GARAGE
CONTROL UNIT FOR SLIDING GATES, SWING GATES, BARRIERS AND GARAGE DOORS
ARMOIRE DE COMMANDE POUR PORTAILS COULISSANTS, BATTANTS, BARRIERES ET PORTES DE GARAGE
CENTRAL ELECTRÓNICA PARA CANCELAS CORREDIZAS, ABATIBLES, BARRERAS Y PUERTAS BASCULANTES
(Cod. 23001158)
Français
Español
tras
Rev.06 - 09/2014

Other manuals for SEA GATE 1 DG R1

Questions and Answers

  • B
    Bryan FloresAug 15, 2025
    What to do if the SEA GATE 1 DG R1 gate is stopped by an obstacle?
    • J
      Jason NavarroAug 15, 2025
      If the SEA Control Unit gate is stopped by an obstacle, the solution is to remove the obstacle.
  • J
    Jason WebbAug 18, 2025
    What to do if there is an ammeter alarm on my SEA GATE 1 DG R1 Control Unit?
    • E
      elizabeth06Aug 18, 2025
      If the SEA Control Unit experiences an ammeter alarm, verify whether the alarm has been triggered and, if necessary, increase the torque parameter.
  • H
    Heather BarryAug 21, 2025
    What to do if the stop contact is open on my SEA Control Unit?
    • D
      david64Aug 21, 2025
      If the stop contact is open on your SEA Control Unit, check the jumpers or the connected devices and the signals indicated on the warning lamp.
  • H
    Hannah SmithAug 25, 2025
    What to do if the edge contact is open on my SEA GATE 1 DG R1 Control Unit?
    • R
      Ronald RodriguezAug 25, 2025
      If the edge contact is open on your SEA Control Unit, check the jumpers or the connected devices and the signals indicated on the warning lamp.
  • P
    pearsonlarryAug 27, 2025
    What to do if the motor is in released position in my SEA GATE 1 DG R1 Control Unit?
    • D
      Derek LongAug 27, 2025
      If the SEA Control Unit motor is in the released position, re-lock the motor.
  • C
    Christina WheelerAug 30, 2025
    What to do if there is a programming error on a SEA GATE 1 DG R1?
    • D
      David OwenAug 30, 2025
      If the SEA Control Unit has a programming error, repeat the programming.
  • S
    Samantha AllisonSep 2, 2025
    What to do if the SEA Control Unit gate opens but doesn’t close?
    • H
      Heather ReynoldsSep 2, 2025
      If the gate opens but doesn’t close, it could be due to several reasons: * The contacts of the photocells are connected and open. * The stop contact is connected and open. * The edge contact is open. * Ammeter alarm. Check the jumpers or the connected devices and the signals indicated on the warning lamp. If the ammeter alarm has intervened, increase the torque parameter.
  • C
    Cody RandolphSep 5, 2025
    How to fix SEA Control Unit gate that doesn’t reach the complete Open / Closed position?
    • E
      ealexanderSep 5, 2025
      If the gate doesn’t reach the complete Open or Closed position, consider the following: 1. The limit switches might be set incorrectly: Set limit switches. 2. There may be an error in programming: Repeat programming. 3. An obstacle may be stopping the gate: Remove obstacle. 4. The torque might be too low: Increase the torque parameter.
  • S
    Sarah BanksSep 8, 2025
    What to do if SEA GATE 1 DG R1 motor doesn’t respond to any START impulse?
    • J
      James MolinaSep 8, 2025
      If the motor doesn’t respond to any START impulse: * Check the connections or the jumpers on the connections of the safety edge or of the stop and of the photocell if connected. * Check the connected N.C. contacts. * If the fuse is burnt, replace the burned fuse on the control unit.
  • S
    Steven CarterSep 12, 2025
    Why SEA GATE 1 DG R1 Control Unit gate doesn’t move while the motor is running?
    • D
      Douglas CrawfordSep 12, 2025
      If the gate doesn’t move while the motor is running: * The motor might be in the released position: Re-lock the motor. * There might be an obstacle: Remove obstacle.

Summary

Components Overview

Connections and Wiring

Programming Quick Start Guide

Language Setup

Procedure to select the user interface language.

Transmitter Programming

Steps for memorizing remote control transmitters.

Motor Setup

Configuration for motor type and operation.

Logic Setup

Selecting the desired operational logic for the gate.

Pause Time Setup

Setting the delay for automatic gate closing.

Start in Pause Setup

Configuring the start behavior during pause.

Programming Cycle

Sequence for executing programming steps.

Test Start Procedure

Initiating a test sequence for programmed functions.

Menu Functions Table

Function Logic Modes

Automatic Logic Description

Operation mode: single impulse opens, second impulse reverses during opening.

Security Logic Description

Operation mode: single impulse opens, second impulse reverses during opening.

Step-by-Step Logic Description

Operation modes for OPEN-STOP-CLOSE sequences.

Control Unit Security

Input Status Check

Radio Transmitter Self Learning

Input Wiring and Functions

Encoder and Amperometric Management

Master-Slave Function

Three-Phase Module Connection

Trouble Shooting Guide

Maintenance and Replacements

Routine maintenance tasks and procedures for replacing parts.

Safety and Environmental Compatibility

Guidelines for product disposal and environmental safety.

Regular Product Disposal

Information on proper disposal of electronic waste.

SEA GATE 1 DG R1 Specifications

General IconGeneral
BrandSEA
ModelGATE 1 DG R1
CategoryControl Unit
LanguageEnglish