SEG Electronics GmbH Technical Manual WIC1
30 DOK-TD-WIC1E, Rev. M
5.7.6 Ambient conditions
Vibration and continuous vibration test
DIN EN 60255-21-1 [05/96] 1/2 gn
Class 2
Shock and continuous shock test
DIN EN 60255-21-2 [05/96] 10/20 gn
Class 2
Earthquake test
DIN EN 60255-21-3 [11/95] 2 gn
Class 2
Classification
DIN EN 60068-1 [03/95] Climate category 40/085/56
Test Ad: Cold
DIN EN 60068-2-1 [03/95] Temperature -40°C
Period of stress 16 h
Test Bd: Dry heat
DIN EN 60068-2-2 [08/94] Temperature +85°C
Rel. humidity <50%
Period of stress 72 h
Test Ca: Humid heat (constantly)
DIN IEC 60068-2-3 [12/86] Temperature +40°C
Rel. humidity 93%
Period of stress 56 h
Test Db :Humid heat (cyclic)
DIN IEC 60068-2-30 [09/86] Temperature +85°C
Rel. humidity 95%
Cyclen (12 + 12-hours) 2
Class of protection Relay housing IP 40
Electronics IP 65
Terminals IP 20