Technical Manual WIC1 SEG Electronics GmbH
DOK-TD-WIC1E, Rev. M 53
7. Product-Specific Features
7.1 Assignment of terminals
The protection relay is equipped with 20 screw-type terminals, make Phoenix and 4 test sockets. The 2 different re-
lay versions are defined by the kind of terminal used:
WIC1-xP plug-in terminals for connection of CTs and trip circuits
Remote trip input for auxiliary voltage 230 V AC
Remote trip input for auxiliary voltage 115 V A*
Remote trip input N (earth)
Centre earthing point WIC1
Electric pulse output +pole
Electric pulse output, -pole
Flag indicator output, +pole
Flag indicator output, -pole
CT measuring winding connection L1
CT measuring winding connection L1
CT test winding connection L1
CT test winding connection L1
CT measuring winding connection L2
CT measuring winding connection L2
CT test winding connection L2
CT test winding connection L2
CT measuring winding connection L3
CT measuring winding connection L3
CT test winding connection L3
CT test winding connection L3
Connection for input test current L1
Connection for input test current L2
Connection for input test current L3
Connection for input test current N (earth)
The terminals 230 V, 115 V, N and PE are provided as fixed terminals.
7.1.1 Earthing
For earthing the WIC connection terminal PE is used.
The measuring winding (terminals S1and S2) of the CTs must not be earthed, oth-
erwise the measurement results are distorted, ensuring in erratic behavior of the
relay. Connection D of the respective test winding can externally be connected with
terminal PE.