16 | Instructions for use
EN
ADDITIONAL AND
SERVICE SETTINGS
INFORMATION GROUP D1 - GENERAL INFORMATION
PARAMETER GROUP P1 - BASIC PARAMETERS
No. Description Range
P1.1
TEMPERATURE DISPLAY ROUND-OFF
With this setting, we can determine to what value the meas-
ured Temp. display will be rounded o.
0 - 0.1 °C
1 - 0.2 °C
2 - 0.5 °C
3 - 1.0 °C
P1.2
AUTOMATIC EXIT TIME
This setting determines the time after which the display returns
to basic mode.
3 ÷ 180 s
(15)
P1.3
DISPLAY ILLUMINATION SHUT-OFF TIME
This setting determines the time after which display lighting is
reduced or shut o.
10 ÷ 180 s
(30)
P1.4
DISPLAY ILLUMINATION OPERATION MODE
This setting determines type of operation of display illumina-
tion.
The following settings are available: 0 - no display illumination.
1- The display has maximum brightness when entering settings
to the room unit. After a delay, display illumination is reduced
to the minimum value.
2- Same as 1, but display illumination is adapted to the amount
of light in the room.
3- Same as 2, but room unit display is completely turned o
in standby mode during night Temp. interval if this occurs
between 6pm and 6am.
0 ÷ 3 (2)
No. Description
d1.1
ROOM UNIT TYPE (RCD1, RCD2 etc.)
d1.2
ROOM UNIT SOFTWARE VERSION
d1.3
TYPE OF CONTROLLER CONNECTED TO ROOM UNIT
WXD10B = 20 WXD10 = 21
WXD20 = 22 WDC10b = 32
WDC10 = 33 WDC20 = 42
KXD10B = 50 KXD10 = 51
KXD20 = 52 KPD10 = 71
KUD10 = 81 CMP25 = 92
d1.4
Software version of the controller
d1.5
Hydraulic scheme of the controller
d1.6
LIGHT SENSOR
Measured light of the room where the room unit is installed is displayed.