8
Service
Fault/error table
Operating Instructions – MOVIMOT
®
flexible
221
Subfault: 16.41
Description: Data of selected motor does not exist
Response: Output stage inhibit
Cause Measure
No startup data set found on the replaceable
memory module for the selected motor.
Check the selection and, if necessary, start up
another motor or replace the memory module.
Subfault: 16.50
Description: Brake parameters not initialized
Response: Output stage inhibit
Cause Measure
No brake data present Check startup
8.6.13 Fault 17 Internal processor fault
Subfault: 17.7
Description: Exception error
Response: Output stage inhibit
Cause Measure
Exception trap in CPU. Contact the SEW‑EURODRIVE Service.
8.6.14 Fault 18 Software error
Subfault: 18.1
Description: Motor management
Response: Output stage inhibit
System state: Fault acknowledgment with CPU reset
Cause Measure
Error detected at motor management interface. – Switch the device off and on again.
– Contact SEW‑EURODRIVE Service if the fault
persists.
Subfault: 18.3
Description: Task system warning
Response: Warning
Cause Measure
Error while processing internal task system. This
may be a timeout for cyclical tasks, for example.
– Acknowledge the warning.
– Contact SEW‑EURODRIVE Service if the warn-
ing occurs regularly.