22
Root device - Association Group 2
Allowed nodes: 9
It is assigned to switch connected to the SW (SW1) terminal (uses Basic command class).
Triggered by SW (SW1). The device sends according to the state of SW (SW1) (switch or push-
button) the command BASIC_SET ON or BASIC_SET OFF to the associated device. This command
is reflected to the output of associated device. Supports the following command classes:
ⓘ NOTE: Depending on which value is set in Parameter 1, the association group will report
differently.
Value 0 (Momentary switch):
• BASIC_SET: depending on previous state, the associated device will be set on or off
Value 1 & 2 (Toggle switch):
• BASIC_SET: depending on the state of the switch, the associated device will be set on or
off
Root device - Association Group 3
Allowed nodes: 9
It is assigned to switch connected to the SW (SW1) terminal (uses Switch Multilevel command
class). Triggered by SW (SW1).
It is recommended to use push buttons for this association. Supports the following command
classes:
ⓘ NOTE: Depending on which value is set in Parameter 1, the association group will report
differently.
Value 0 (Momentary switch):
• SWITCH_MULTILEVEL_START_LEVEL_CHANGE: initiate a transition to a new level
(increase or decrease light intensity in case of dimmer, or move shutter up or down, …)
• SWITCH_MULTILEVEL_STOP_LEVEL_CHANGE: stop an ongoing transition (stop increase
or decrease light intensity in case of dimmer, or stop moving shutter up or down, …)
Value 1 & 2 (Toggle switch):
• SWITCH_MULTILEVEL_START_LEVEL_CHANGE: does not report
• SWITCH_MULTILEVEL_STOP_LEVEL_CHANGE: does not report