What to do if program control does not start on my Shinko Controller?
- MmcooperSep 2, 2025
If program control does not start even when the key is pressed in Program mode on your Shinko Controller, ensure that the step time has been set.
What to do if program control does not start on my Shinko Controller?
If program control does not start even when the key is pressed in Program mode on your Shinko Controller, ensure that the step time has been set.
Why can't I select the setting mode on my Shinko FCR-13A Controller?
If the setting mode cannot be selected on your Shinko Controller, it might be because Manual control is selected. Change the mode to Automatic control.
Why can't I change the setting indication on my Shinko FCR-13A Controller?
If the setting indication on your Shinko Controller does not change even when pressing the keys, and you are unable to set new values, the SV high limit or SV low limit in Auxiliary function setting mode 1 may be set to a point where the value does not change. Set it to a suitable value in Auxiliary function setting mode 1.
What does it mean if the PV display is indicating nothing or only PV on my Shinko Controller?
If the PV display on your Shinko Controller shows no indication or only PV, it's possible that the Control output OFF function is enabled. To release this function, press the key for approximately 1 second.
What to do if control is not performing on my Shinko FCR-13A?
If control is not performing on your Shinko Controller and only the PV display is indicated, the Control output OFF function might be active. Press the key to cancel this function. Alternatively, Program mode might be selected. To start Program control, press the key. For Fixed value control, press the key for approximately 3 seconds while holding down the key.
What causes the PV display to flash on a Shinko FCR-13A Controller?
If the PV display on your Shinko Controller is flashing, ensure that the polarity of the thermocouple or compensating lead wire is correct. Also, check whether the RTD codes (A, B, B) match the instrument terminals.
Why is the PV display indication irregular or unstable on my Shinko Controller?
If the PV display indication on your Shinko Controller is irregular or unstable, ensure that a suitable sensor input has been selected using the Rotary switch (SW303) and DIP switch (SW304). Also, verify that the temperature unit is correct using the DIP switch (SW304), the sensor correction value is appropriate, the thermocouple or RTD specification is correct, there is no AC leakage into the thermocouple or RTD circuit (use an ungrounded sensor), and that there is no interfering equipment near the controller.
Why is the PV not rising on my Shinko FCR-13A?
If the PV on your Shinko Controller isn't rising, one potential cause is a burnt-out thermocouple or RTD. Try replacing the sensor. Also, check that the sensor or control output terminals are securely mounted and correctly wired to the instrument terminals.
Output Type | Relay, Voltage pulse |
---|---|
Display | 7-segment LED |
Power Supply | 100 to 240 VAC |
Mounting | Panel mount |
Power | 5 VA |
Frequency | 50/60 Hz |
Operating Temperature | 0 to 50°C |
Storage Temperature | -20 to 65°C |
Protection | IP66 front panel |
Dimensions | 48 x 48 x 78 mm |
Weight | Approx. 150g |
Lists abbreviations used throughout the instruction manual for clarity.
Details the characters used for indications and alphabets in the manual.
Provides general notes, warnings, cautions, and prohibitions for using the instrument.
Details critical safety precautions for handling and operating the controller.
Information regarding the ordinance for exporting trade control of the instrument.
Specifies precautions to be taken during the installation of the controller.
Outlines essential precautions to follow during the wiring process.
Details precautions for operating and maintaining the controller safely.
Explains how to identify the controller model and its available options.
Lists the standard specifications of the FCR-13A controller.
Details the various optional specifications available for the controller.
Provides the rated input ranges for different sensor types.
Guides users on interpreting the information on the controller's model label.
Describes the function of each display indicator on the controller's front panel.
Explains the function and operation of each key on the controller's keypad.
Instructions on how to safely remove the internal assembly from the controller case.
Details on setting DIP and rotary switches for various functions.
Guidelines for selecting an appropriate mounting location for the controller.
Provides the external dimensions of the controller in millimeters.
Specifies the dimensions required for the control panel cutout.
Provides the dimensions of the current transformers (CT) used with the controller.
Instructions for installing the one-touch and screw-type mounting brackets.
Details on using solderless terminals with M3 screws for wiring.
Illustrates the terminal arrangement and explains various input/output options.
Provides a wiring example for the FCR-13A controller with R/M model.
Provides a wiring example for the FCR-13A controller with S/M, W models.
Details on wiring current transformers for heater burnout alarm.
Visual flowchart detailing the controller's operation and setting sequences.
Describes the main setting mode for configuring controller parameters.
Details the sub setting mode for accessing specific parameter configurations.
Covers auxiliary functions such as set value lock and sensor correction.
Details advanced auxiliary settings like scaling and hysteresis.
Provides essential notes and considerations before operating the controller's keys.
Explains the set value lock function and its different lock levels.
Details settings for SV limits, sensor correction, and overlap/dead bands.
Describes how to configure remote or local setting methods for SV.
Covers settings for instrument number, communication speed, and protocol.
Details settings within Auxiliary Function Mode 2, including scaling.
Configuration for decimal point display and PV filter time constant.
Details on setting high/low limits and hysteresis for OUT1.
Configuration for OUT2 action mode and high/low limit settings.
Settings for OUT2 hysteresis and alarm action (Energized/De-energized).
Configuration for delay times for Alarm 1 and Alarm 2 actions.
Details on configuring external analog signals for SV input.
Configuration for transmission output types and limits.
Settings for indication when output is OFF and SV rise/fall rates.
Settings for SV fall rate and output status during input errors.
Overview of the controller's program mode functionality.
How to switch between fixed value and program control modes.
Instructions for setting the duration for each step in program control.
Details on switching between auto/manual control and using output OFF function.
How to display MV and remaining step time on the controller.
Describes terminal connections for selecting set value memory numbers.
Steps for operating the set value memory function.
Explains how to register data into the set value memory.
Step-by-step guide for operating the controller as a temperature controller.
Instructions for operating the controller as a simplified programmable controller.
Explains the standard control actions for OUT1 (Heating/Cooling).
Details the optional heater burnout alarm action.
Describes the ON/OFF control action for OUT1 with hysteresis.
Explains the pattern end action and its output behavior.
Details the basic heating and cooling control actions.
Explains how to set a dead band for control actions.
Describes setting an overlap band with relay contact output.
Explains the action logic for Alarm 1 and Alarm 2.
Explains the principles of fuzzy self-tuning for automatic PID adjustment.
Details the fundamentals of PID control actions: Proportional, Integral, Derivative.
Describes the AT process, its fluctuations, and conditions affecting completion.
Summarizes the standard specifications including mounting, display, and accuracy.
Details specifications for Alarm 2 and Heating/Cooling control options.
Lists common PV display indications and their possible causes/solutions.
Addresses issues related to keypad operations and setting parameter problems.
Covers problems related to control performance and output status.
Provides a character table mapping settings to their respective parameters.