EasyManuals Logo

Sices GC315 User Manual

Sices GC315
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #169 background imageLoading...
Page #169 background image
GC315xx and GC400xx Technical Manual 169
Enabled in: MAN, AUTO, TEST, REMOTE START
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated) It is enabled the first time (from engine start) the generator's
frequency and voltages enter the tolerance range (see generator sequence description). In
MAN it is only enabled if the GCB breaker is closed. It is enabled if, under the conditions
previously mentioned, at least one of the generator voltages is continuously below the
threshold P.0301 for the time P.0302.
Type: Alarm
Category: Load/generator protection
Related parameters: P.0101 Number of generator phases
P.0102 Nominal voltage of the generator
P.0202 Generator measures hysteresis
P.0303 Maximum voltage threshold
P.0304 Maximum voltage delay
P.0328 Enables checks including on the phase voltages
To disable: P.0304=0
Enabled in: MAN, AUTO, TEST, REMOTE START
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated) It is enabled if, under the conditions previously mentioned, at
least one of the generator voltages exceeds continuously the threshold P.0303 for the time
P.0304.
Type: Deactivation
Category: Load protection
Related parameters: P.0105 Rated frequency
P.0305 Minimum frequency threshold
P.0306 Minimum frequency delay
To disable: P.0306=0
Enabled in: MAN, AUTO, TEST, REMOTE START
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated) It is enabled the first time (from engine start) the generator's
frequency and voltages enter the tolerance range (see generator sequence description). In
MAN it is only enabled if the GCB breaker is closed. It is enabled if, under the conditions
previously mentioned, the generator frequency is continuously below the threshold P.0305 for
the time P.0306.
Type: Alarm
Category: Load/generator protection
Related parameters: P.0105 Rated frequency
P.0307 Maximum frequency threshold
P.0308 Maximum frequency delay
To disable: P.0308=0
Enabled in: MAN, AUTO, TEST, REMOTE START

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sices GC315 and is the answer not in the manual?

Sices GC315 Specifications

General IconGeneral
BrandSices
ModelGC315
CategoryController
LanguageEnglish

Related product manuals