Parameter
name
Attrib‐
utes
Acces
s
Data
type
Information
Validation/
Backup (is
only consid‐
ered in port
mode
IOL_Manual)
2 Get/S
et
USINT 0: no Device
check
No device inspection: No inspection
is performed on this IO-Link port
regarding the correct device ID, man‐
ufacturer ID or serial number.
1: type com‐
patible device
(V1.0)
Type-compatible device (V1.0): An
inspection is performed on the IO-
Link port with regard to the correct
IO-Link revision (V1.0), device ID and
manufacturer ID.
2: type com‐
patible device
(V1.1)
Type-compatible device (V1.1): On
the IO-Link port, an
inspection concerning the revision
ID, device ID and
manufacturer ID is done.
3: type com‐
patible V1.1
device with
Backup +
Restore
Type-compatible device (V1.1) with
backup + restore: An inspection is
performed on the IO-Link port with
regard
to the revision ID, device ID and man‐
ufacturer ID. Data storage (reading
and writing) is permitted.
4: type com‐
patible V1.1
device with
Restore
Type-compatible device (V1.1) with
restore: On the IO-Link port, an
inspection is performed with regard
to the revision ID, device ID and man‐
ufacturer ID. Data storage (writing) is
allowed.
I/Q Behavior 3 Get/S
et
USINT 0: deacti‐
vated
Configuration of pin 2 behavior.
1: Digital
Input
2: Digital Out‐
put
NOTE
Power AUX allows the support of class B devices with
additional voltage supply (Ua), but without galvanic
separation.
Port cycle
time
4 Get/S
et
USINT 0: as fast as
possible
IO-Link cycle time (is only considered
in port mode IOL_Manual)
Cycle time = multiplier * time base
Bit 0 – 5 Multiplier
Bit 7 6 Time base
0 0 0.1ms
0 1 6.4ms
1 1 32ms
1-255: time
Vendor ID (is
only consid‐
ered in port
mode
IOL_Manual)
5 Get/S
et
UINT Expected manufacturer ID of the IO-Link device con‐
nected to the IO-Link port (unsigned integer 16)
Example:
Manufacturer ID SICK AG = 26
8 OPERATION
36
O P E R A T I N G I N S T R U C T I O N S | Sensor Integration Gateway - SIG350 8027834./2022-06-10 | SICK
Subject to change without notice