For IO-Link ports (Slot 2, subslots 2…5) different process data submodules are avail‐
able. Data is represented in the following format:
Submdule
name
Direc‐
tion
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Digital input In 0 0 0 0 0 0 0 0 SxDI1
Digital output Out 0 0 0 0 0 0 0 0 SxDO
1
IO-Link 2I / 0O
+ PQI
In 0 2 byte IO-Link Process Data In
1
2 PQI
IO-Link 0I / 2O
+ PQI
In 0 PQI
Out 0 2 byte IO-Link Process Data Out
1
IO-Link 2I / 2O
+ PQI
In 0 2 byte IO-Link Process Data In
1
2 PQI
Out 0 2 byte IO-Link Process Data Out
1
IO-Link 4I / 0O
+ PQI
In 0 4 byte IO-Link Process Data In
…
3
4 PQI
IO-Link 0I / 4O
+ PQI
In 0 PQI
Out 0 4 byte IO-Link Process Data Out
…
3
IO-Link 4I / 4O
+ PQI
In 0 4 byte IO-Link Process Data In
…
3
4 PQI
Out 0 4 byte IO-Link Process Data Out
…
3
IO-Link 8I / 0O
+ PQI
In 0 8 byte IO-Link Process Data In
…
7
8 PQI
IO-Link 0I / 8O
+ PQI
In 0 PQI
Out 0 8 byte IO-Link Process Data Out
…
7
7 SIG200 CONFIGURATION
22
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200 8017853/2019-06-06 | SICK