Two-State Constant Volume
Fume Hood Controller
Owner’s Manual
125-5033 Rev. AA, September 2007
Question and Answer IconNeed help?

Do you have a question about the Siemens 125-5033 and is the answer not in the manual?

Siemens 125-5033 Specifications

General IconGeneral
Supply voltage24 V DC
Analog inputs2
Mounting typeDIN rail
Trip Unit TypeNot applicable
Interrupting RatingNot applicable
MountingDIN rail

Summary

Product Overview

Ordering Notes

Details the ordering information for the Fume Hood Controller - Electronic Output (940).

Controller Hardware Inputs and Outputs

Details the analog and digital inputs and outputs for the Fume Hood Controller.

Controller Indicators and Operator Interface

Explains the controller's LEDs and the Operator Display Panel (ODP) functions.

Airflow Measurement Components

Describes the Laboratory Exhaust Air Terminal, Venturi Air Valves, DP Transmitter, and Airflow Sensor.

Actuation Systems

Covers Electronic and Pneumatic Actuation methods, including the AO-P Module.

Applications

Fume Hood Controller: 2-Position Constant Volume

Describes Application 940 for controlling two-position fume hoods in a manifolded exhaust system.

Basic Operation

High and Low Exhaust Flow Control

Explains how the controller operates at two setpoints: HI flow and LOW flow, including OFF mode.

Control Loops and Signal Modulation

Describes the PID loop control for exhaust flow and signal modulation for electronic/pneumatic outputs.

Warning and Alarm Features

Details how the controller indicates performance problems at WARNING and ALARM levels.

Emergency Purge Feature and Operation

Describes the Emergency Purge sequence, its initiation, cancellation, and indicators.

Fail-safe Operation

Describes failure modes for the controller and its accessories, and how the system behaves upon failure.

Point Database

Application and Alarm Points

Describes points for controller application identification and alarm status (LOW, HIGH, EMER ALM).

Flow Control Setpoints and Readings

Details points for airflow setpoints (FLOW STPT) and calculated exhaust flow (EXH FLOW).

Input and Display Points

Describes analog inputs (AI1 DP TRANS) and ODP display control points.

Troubleshooting

Basic Service Information

Provides essential safety information for installing or replacing the controller, including power removal.

Preventive Maintenance and Safety Features

Recommends maintenance discussions and explains data storage for safety.

Controller LED Indicators

Details how to verify controller operation using the Basic Sanity Test (BST) LED and other indicators.

Glossary

Key Control Terms

Defines essential terms like AI, DDC, DI, DO, FLN, PID, and Equipment Controller.