11 Testing the Tripping Solenoid
The overcurrent release must be mounted in the circuit breaker to
carry out this test.
The circuit breaker must be switched on.
In order to test the tripping solenoid, start any one of the tests
described above and wait for the tripping command of the
overcurrent release. The circuit breaker must switch off in the
process.
If the circuit breaker does not switch off, the following causes may
apply:
- The connecting cable (X22) for the tripping solenoid has not
been plugged in correctly
- The tripping solenoid is defective
- Faulty coordination between the tripping solenoid and the
switch latching
- Overcurrent release is defective
11 Prüfung des Auslösemagneten
Für diese Prüfung muss der Überstromauslöser in den Leistungs-
schalter eingesetzt sein.
Der Leistungsschalter muss eingeschaltet sein.
Zur Prüfung des Auslösemagneten eine beliebige der beschriebe-
nen Prüfungen einleiten und das Auslösekommando des Über-
stromauslösers abwarten. Dabei muss der Leistungsschalter
abschalten.
Wird der Schalter nicht ausgeschaltet, sind folgende Ursachen
möglich:
- Anschlussleitung des Auslösemagneten (X22) nicht richtig
eingesteckt
- Defekter Auslösemagnet
- Fehler im Zusammenwirken zwischen Auslösemagnet und
Schalterverklinkung
- Fehler im Überstromauslöser