9 – 3
9.2 Prüfung der Erdschlussauslösung bei
Anschluss eines externen
Erdschlussstromwandlers, Messmethode
„Direkte Messung des Erdschlussstromes“
Mit der Taste MODE (1) die Betriebsart GF wählen.
Mit dem Potentiometer EXTERNAL GF CT CURRENT (4) den erfor-
derlichen Prüfstrom einstellen (1 A entspricht dabei einem
Erdschlussstrom von 1200 A). Dazu den Taster CURRENT
ADJUST während des Einstellvorgangs betätigen.
9.2.1 Unterer Grenzwert
Prüfstrom gemäß I
p
= 0.8 * I
g
einstellen.
I
p
= Prüfstrom
I
g
= Ansprechwert des kurzzeitverzögerten Erdschlussauslösers (g)
bei Verwendung eines externen Summenstromwandlers (ext.g)
Prüfvorgang mit Taster TEST ENABLED (9) vorbereiten und mit
Taster START/STOP (10) einleiten.
Bei dieser Prüfung darf der kurzzeitverzögerte Erdschlussauslöser
(G) nicht ansprechen.
Prüfvorgang mit dem Taster START/STOP (10) abbrechen.
9.2.2 Oberer Grenzwert
Prüfstrom gemäß I
p
= 1.2 * I
g
einstellen.
I
p
= Prüfstrom
I
g
= Ansprechwert des kurzzeitverzögerten Erdschlussauslösers bei
Verwendung eines externen Summenstromwandlers
Prüfvorgang mit Taster TEST ENABLED (9) vorbereiten und mit
Taster START/STOP (10) einleiten.
Bei dieser Prüfung muss der kurzzeitverzögerte Erdschlussauslöser
(G) ansprechen.
9.2.3 Prüfung der Verzögerungszeit
In Abhängigkeit der Zeitmessmethode nach 5.1 sind bei der Ermitt-
lung der Verzögerung folgende Zeiten des Leistungsschalters zu
berücksichtigen:
- Aktivierung der ETU 15 ms
- Schaltereigenzeit ca. 20 ms
Diese sind ggf. von der gemessenen Auslösezeit abzuziehen.
9.2.3.1 Stromunabhängige Verzögerung, t
g
= fix
Diese Prüfung wird angewendet, wenn die I
2
t
g
-abhängige Verzöge-
rung (I
2
t
g
=const) und "ZSS" abgeschaltet sind.
Prüfstrom I
p
= 1.5 * I
g
mit Potentiometer EXTERNAL GF CT
CURRENT (4) und TASTER ADJUST (7) einstellen.
I
p
= Prüfstrom
I
g
= Ansprechwert des kurzzeitverzögerten Erdschlussauslösers
Prüfvorgang mit Taster TEST ENABLED (9) vorbereiten und mit
Taster START/STOP (10) einleiten.
Die Toleranz für die Verzögerungszeit beträgt t
g
+50 ms.
9.2 Testing the Ground-fault Release when an
External Ground-fault Current Transformer is
Connected using the Measuring Method “Direct
Measurement of the Ground-fault Current”
Select operating mode GF by means of the MODE pushbutton (1).
Set the required test current by means of the EXTERNAL GF CT
CURRENT potentiometer (4) (1 A is equivalent to a ground-fault
current of 1,200 A). Continuously press the CURRENT ADJUST
pushbutton when setting the test current.
9.2.1 Lower Limit Value
Set test current according to I
p
= 0.8 * I
g
.
I
p
= test current
I
g
= response threshold of the short-time-delay ground-fault release
(g) when using an external summation current transformer (ext.g).
Enable testing by pressing the TEST ENABLED pushbutton (9), and
start testing by pressing the START/STOP pushbutton (10).
The short-time-delay ground-fault release (G) should not respond
during this test.
Testing can be interrupted by pressing the START/STOP
pushbutton (10).
9.2.2 Upper Limit Value
Set test current according to I
p
= 1.2 * I
g
.
I
p
= test current
I
g
= response threshold of the short-time-delay ground-fault release
when using an external summation current transformer
Enable testing by pressing the TEST ENABLED pushbutton (9), and
start testing by pressing the START/STOP pushbutton (10).
The short-time-delay ground-fault release (G) must respond during
this test.
9.2.3 Testing the Delay Time
Depending on the time measuring method applied as described in
5.1, the following circuit-breaker times should be taken into
consideration when measuring the delay:
- ETU activation 15 ms
- Switch response time approx. 20 ms
If necessary, these are to be subtracted from the measured tripping
time.
9.2.3.1 Current-independent delay, t
g
= fixed
This test is implemented when the I
2
t
g
dependent delay (I
2
t
g
=
const) and “ZSI” are switched off.
Set the test current I
p
= 1.5 * I
g
by means of the EXTERNAL GF CT
CURRENT potentiometer (4) and the ADJUST pushbutton (7).
I
p
= test current
I
g
= response threshold of the short-time-delay ground-fault release
Enable testing by pressing the TEST ENABLED pushbutton (9), and
start testing by pressing the START/STOP pushbutton (10).
The delay time tolerance is t
g
+50 ms.