Article number 6ES7515-2AN03-0AB0
Status block Yes; Up to 8 simultaneously (in total across all ES
clients)
Single step No
Number of breakpoints 8
Status/control
•
Status/control variable Yes
•
Variables Inputs/outputs, memory bits, DBs, distributed
I/Os, timers, counters
•
Number of variables, max.
–
of which status variables, max. 200; per job
–
of which control variables, max. 200; per job
Forcing
•
Forcing Yes
•
Forcing, variables Peripheral inputs/outputs
•
Number of variables, max. 200
Diagnostic buffer
•
present Yes
•
Number of entries, max. 3200
–
of which powerfail-proof 500
Traces
•
Number of configurable Traces 4; Up to 512 KB of data per trace are possible
Interrupts/diagnostics/status information
Diagnostics indication LED
•
RUN/STOP LED Yes
•
ERROR LED Yes
•
MAINT LED Yes
•
STOP ACTIVE LED Yes
•
Connection display LINK TX/RX Yes
Supported technology objects
Motion Control Yes; Note: The number of technology objects
affects the cycle time of the PLC program; selec
tion guide via the TIA Selection Tool
•
Number of available Motion Control
resources for technology objects
2400
•
Required Motion Control resources
–
per speed-controlled axis 40
–
per positioning axis 80
–
per synchronous axis 160
–
per external encoder 80
–
per output cam 20
48
CPU 1515-2 PN (6ES7515-2AN03-0AB0)
Equipment Manual, 11/2022, A5E46416198-AC
Technical specifications