09.02  Parameter List 
Siemens AG    6SE7087-6AK85-1AA0 
5-21 
Rectifier/Regenerating Unit    Operating Instructions 
PNU 
 
*
 
: Conf. 
    Par. 
OP1S parameter name 
 
Description 
Value range  
[phys. unit] 
Selection text 
Display 
Indices 
Factory- 
setting 
See 
Modify 
(access / 
status) 
P575 
* 
Src No ExtFault1 
Source for the "External fault 1" control command (control word 1, bit 15) 
L signal causes disconnection of the faulted drive. 
 
0: Not allowed 
1:  No external fault 1 
1003: Binary input 3 of the CUR board 
Other values: 
see allowed settings in Section 4.3.1.1 (process data 
wiring of the control word) 
 
B/R parameter 
 
PNU=23FHex; Type=L2; Scaling: 1Hex 
=
∧
 1 
1 to 6005  2 
(1) 
2/    BR 
2/    BR 
P578 
* 
Src RDataSetBit0 
Source for bit 0 (control word 2, bit 18) for selecting the reserve data set 
(RDS) 
 
0:  RDS bit 0 has the value 0 
1:  RDS bit 0 has the value 1 
Other values: 
see allowed settings in Section 4.3.1.1 (process data 
wiring of the control word) 
 
B/R parameter 
 
PNU=242Hex; Type=L2; Scaling: 1Hex 
=
∧
 1 
0 to 6005  2 
0 
3/    BR 
3/    BR 
P579 
* 
Src RDataSetBit1 
Source for bit 1 (control word 2, bit 19) for selecting the reserve data set 
(RDS) 
 
0:  RDS bit 1 has the value 0 
1:  RDS bit 1 has the value 1 
Other values: 
see allowed settings in section 4.3.1.1 (process data 
wiring of the control word) 
 
B/R parameter 
 
PNU=243Hex; Type=L2; Scaling: 1Hex 
=
∧
 1 
0 to 6005  2 
0 
2/    BR 
2/    BR 
P583 
* 
Src 12-Pulse Mode 
Source for control command "12-pulse mode is selected" (control word 2, bit 
23) 
 
0:  No 12-pulse mode 
1:  12-pulse mode is selected 
Other values: see allowed settings in section 4.3.1.1 (process data 
wiring of the control word) 
 
B/R parameter 
 
PNU=247Hex; Type=L2; Scaling: 1Hex 
=
∧
 1 
1 to 6005  2 
(0) 
3/    BR 
3/    BR 
P586 
* 
Src No ExtFault2 
Source of the 'External fault 2' message (control word 2, bit 26) 
L signal causes disconnection of the faulted unit after a pre-charging time of 
+ 200ms if the rectifier/regenerating unit is in the "RUN" status. 
 
0: Not allowed 
1:  No external fault 
1004: Binary input 4 of the CUR board 
Other values: see allowed settings in Section 4.3.1.1 (process data 
wiring of the control word) 
 
B/R parameter 
 
PNU=24AHex; Type=L2; Scaling: 1Hex 
=
∧
 1 
1 to 6005  2 
1 
2/    BR 
2/    BR 