05.2005 Start-up
Siemens AG 6SE7087-2NP85-0AA0
SIMOVERT MASTERDRIVES Operating Instructions 3-1
3 Start-up
3.1 Start-up steps
After removing the packaging, please check that the unit
is intact and undamaged. Only intact units may be
started-up. Please also check that the unit is complete.
Unpack and
check the unit
See section
"Transport,
Storage,
Unpacking"
Mount the unit in conformance with the requirements at
the point of installation and the EMC instructions.
Mount the unit
See section
"Installation" and
"Installation in
Conformance
with EMC
Regulations"
Starting with the protective conductor, please connect
the supply cable, the external braking resistor and the
external 24 V incoming supply. When laying the cables,
please observe the EMC instructions. During this work
step, please do not yet connect the DC link buses.
Connect the
protective conductor,
the supply cable, the
external braking resistor
and the external 24 V
incoming supply
See section
"Connecting-up"
and "Installation
in Conformance
with EMC
Regulations"
111
Power up the external
24 V incoming supply
111
After powering up the line voltage, the LED "Run" will
light up on the rectifier unit.
Power up the
line voltage,
carry out function test
111
111
De-energize the line
voltage and the external
24 V incoming supply
111
Connect the DC link buses and form the connection to
the converters.
Connect the DC link
See section
"Connecting-up"